Digital inputs/outputs
The 18 digital pins can be configured by software as inputs or outputs in groups of 4 (D0..D3, D4..D7,
D9..D12, D13..D16) or individually (D8 and D17).
Analog inputs
The module provides 4 analog differential inputs with 12 bit resolution. Module Version /U supports
4 ranges (0...5 Volt, 0...10 Volt, +-5 Volt, +-10 Volt).
A gainfactor (1 ... 1000) can be set for each channel by inserting a resistance.
Module version /i has 4 current inputs (0...20 mA).
In addition 4 internal signals can be measured:
5V reference voltage, 3,3V power supply, analog ground and module temperature.
Analog outputs
Module version /U supports 4 different ranges (0...5 Volt, 0...10 Volt, +-5 Volt, +-10 Volt) per
channel.
Module version /i supports current outputs (0...20 mA).
Block diagram
Technical data
Parameter
Value
Unit
Analog inputs:
- Number
4
-
- Resolution
12
Bit
- Conversion time, min./typ./max.
6/7,7/10
µs
- Acquisition Time, min./max.
3/5
µs
- Input ranges, version /U
0...5, 0...10, -5...5, -10...10
V
- Input ranges, version /i
0...20
mA
- Common Mode Range, version /U
+-10
V
- Overvoltage protection, version /U
+-40
V
- Input impedance (Common Mode/Diff.), version /U
>100/>100
MOhm
Analog outputs:
- Number
4
-
- Resolution
12
Bit
- Settle Time, max.
3
µs
- Output ranges, version /U
0...5, 0...10, -5...5, -10...10
V
- Output ranges, version /i
0...20
mA
Digital inputs/outputs (4 groups with 4 I/Os and 2 single I/Os, each selectable
as input or output):
- Number
18
-
- Input voltage log. 0
<0,8
V
- Input voltage log. 1
>2,0
V
- Input Leakage Current, max.
10
mA
- Output voltage log. 0, max. (IOL=8mA)
0,4
V
- Output voltage log. 1, min. (IOH=-4mA)
2,4
V
- Output current, max. log.0
-12
mA
- Output current, min. log.1
+12
mA
- Overvoltage protection of inputs
-0,5...5,5
V
- Overvoltage protection of inputs for pulses <10ns und <200mA